Enclosure: 12-way flush mount design with a durable white plastic front cover and a robust galvanised steel tray/back box for in-wall installation. Features a transparent, smoked, hinged inspection door.
Mains Protection: Includes 1 x CHINT NXBLE-63Y 63A 30mA Type C RCBO (Residual Current Breaker with Overcurrent protection), 4-module width, with 6kA breaking capacity.
Circuit Protection (MCBs):
1 x CHINT eBC 32A Type C Miniature Circuit Breaker (MCB) with 3kA breaking capacity.
3 x CHINT eBC 20A Type C Miniature Circuit Breakers (MCB) with 3kA breaking capacity.
2 x CHINT eBC 10A Type C Miniature Circuit Breakers (MCB) with 3kA breaking capacity.
Spare Ways: 2 spare ways available for future circuit additions.
DIN Rail: Pre-fitted standard 35mm DIN rail within the steel tray.
Standards Compliant: Components comply with relevant IEC standards (IEC61009-1 for RCBO, IEC/EN 60898-1 for MCBs).
Certification: Components are CE marked.
Easy Access: Numbered positions (1-12) for clear circuit identification.
Neat, Integrated Appearance: Flush mounting provides a discreet, built-in look that blends seamlessly with interior walls.
Time-Saving Installation: Pre-populated with essential breakers, reducing installation time and complexity.
Enhanced Durability: Galvanised steel tray offers increased rigidity, mechanical protection, and longevity for the enclosure.
Superior Safety: The 4-module RCBO main switch provides critical protection against earth faults, overloads, and short circuits.
Versatile Circuit Management: A range of MCB ratings caters to diverse circuit requirements.
Future-Proof: 2 spare ways allow for straightforward expansion as electrical needs grow.
Convenient Monitoring: Transparent cover allows for immediate visual inspection of breaker status.
Trusted Brand: CHINT components are known for their quality, reliability, and adherence to international safety standards.
Type: Flush Mount Consumer Unit / Distribution Board
Ways: 12 Total Ways (10 Populated, 2 Spare)
Material:
Front Cover Assembly: High-impact thermoplastic (Body: White, Inspection Door: Smoked Transparent)
Back Box/Tray: Galvanised Steel
Mounting: Pre-installed 35mm DIN Rail in steel tray
Model: NXBLE-63Y
Type: Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO)
Module Width: 4 Ways (e.g., 2P configuration occupying approx. 72mm)
Rated Current (In): 63A
Rated Residual Operating Current (IΔn): 30mA (0.03A)
Tripping Curve: Type C
Rated Voltage (Ue): 230V AC (typical for 1P+N or 2P single phase)
Frequency: 50/60Hz
Rated Short-circuit Breaking Capacity (Icu/Ics): 6000A (6kA)
Rated Impulse Withstand Voltage (Uimp): 4kV
Standard: IEC61009-1
Mechanical Life: 20,000 cycles
Electrical Life: 10,000 cycles
Certification: CE
Model: eBC
Type: Miniature Circuit Breaker (MCB)
Poles: 1P
Included Ratings & Quantities:
1 x 32A
3 x 20A
2 x 10A
Tripping Curve: Type C (5-10In)
Rated Voltage (Ue): 230/400V AC
Rated Short-circuit Breaking Capacity (Icn): 3kA (as per eBC specification for 1-63A)
Rated Impulse Withstand Voltage (Uimp): 4kV
Standard: IEC/EN 60898-1
Electrical Life: 4,000 cycles
Mechanical Life: 10,000 cycles
Protection Degree (Breaker itself): IP20
Terminal Connection Type: Cable/Pin-type busbar
Terminal Size (Cable): 1-25 mm²
Mounting: On DIN rail EN 60715 (35mm)
Certifications: CE, SAA, etc. (as per datasheet)
Residential Properties: Ideal for new builds or renovations where a clean, unobtrusive installation is desired.
Modern Apartments and Condominiums: Provides a sleek finish in living spaces.
Small Commercial Spaces: Suitable for offices and retail units requiring a professional, integrated look.
Installations requiring enhanced mechanical protection for the enclosure back box within the wall.
Applications where aesthetic integration into the building fabric is important.
Professional Installation: Installation must be carried out by a qualified and certified electrician, ensuring compliance with local electrical codes and flush-mounting best practices.
Accurate Wall Recess: Ensure the wall opening (cut-out) is prepared to the correct dimensions for the galvanised steel tray to ensure a proper fit and secure installation.
RCBO Testing: Regularly test the RCBO function using the "T" or "Test" button (typically monthly) to ensure it is operating correctly.
Load Balancing: When adding new circuits, consult your electrician for proper load balancing and to ensure the total load does not exceed main switch capacity.
Correct Cable Sizing: Use appropriate cable sizes for each circuit according to its current rating and length.
Secure Connections: Verify all terminal connections are tightened to the manufacturer's recommended torque settings.
Clear Labeling: Label each circuit clearly for easy identification and maintenance.